AC FFU Control System
Install Diagrain for Power Line
FFU-M15
Model
|
M15 (Adjustable)
(2'x4' FFU)
|
M15
(2'x4' FFU)
|
M20
(2.5'x5' FFU)
|
M26
(4'x4' FFU)
|
Main Unit
|
Aluminum housing (Standard),Stainless bright finish (Option)
|
Dimensions (mm)
|
577(W)x1,177(L) |
727(W)x1,477(L) |
1,177(W)x1,177(L) |
Power Supply
|
AC single-phase 110V/220V 60Hz
|
AC three-phase 220V/380V
60Hz
|
Speed Level
|
High speed
|
Medium speed
|
Low speed
|
Single speed
|
Currency Consumption A
|
1.3/0.65 |
1.05/0.55 |
0.965/0.5 |
0.48/0.28 |
0.54/0.32 |
0.87/0.48 |
Power Consumption
VA
|
145 |
115 |
106 |
185 |
210 |
335 |
Fan Total Pressure
mmAq
|
28 |
26 |
24 |
26 |
28 |
46 |
Wind Velocity
M/S
|
0.46 |
0.38 |
0.31 |
0.4 |
0.34 |
0.33 |
Air Volume
CMM
|
17 |
14 |
11.5 |
15 |
20 |
26 |
Noise dBA
|
52 |
48 |
44 |
50 |
52 |
58 |
Motor Output W
|
80 |
70 |
90 |
125 |
Pole of Motor
|
6 poles
|
Class of Insulation
|
E Class
|
Speed RPM
|
1,110 |
1,000 |
900 |
1,050 |
1,100 |
1,300 |
Motor Efficiency %
|
58.5 |
56.5 |
47 |
57.5 |
64 |
44 |
Trip Indicator
|
Built-in(red light)
|
Overload
Protection Switch
|
Built-in(may be paired up with mounted terminal block)
|
Weight Kg
|
About 32Kg (Main unit: :24.5+Filter7.5)
|
About 39.5Kg
(Main unit: 30+Filter9.5)
|
About 51Kg
(Main unit: 36+Filter15)
|
Filter Dimensions
|
570mm x 1,170mm |
720mm x 1,470mm |
1,170mm x 1,170mm |
Grid Dimensions
|
600mm x 1,200mm |
750mm x 1,500mm |
1,200mm x 1,200mm |
Note: Above data have been the results tested by measuring equipments established in accordance with USA AMCA210-85 regulations.
Features:
-
Lightweight and thinner unit
Height of the unit including main filter is only 120mm with only 5Kg (MK-0250E) weight, which is even suitable for locations with lower ceilings.
-
High-efficiency, backward centrifugal fan
External-rotor motor designed with computerized analysis, providing high wind level, high hydrostatic pressure, higher efficiency and lower noise.
-
Elegant and friendly designs
With main filter, easy in transportation and installation with more elegant appearance.
-
Flexible and diversified consideration
Besides standard models, modification can be made based on customers’ requirements, such as: change in types of filter, unit materials, etc.
-
Multiple safety devices (option)
Overload protector, motor built-in protective switch, failure indicator light, failure signal loop, etc.
|
Specifications
Model
|
一 |
MS-250 |
MS-400 |
MS-400T |
MS-500 |
MS-600 |
MS-900 |
MS-1200 |
Outer Dimensions
|
W |
mm |
250 |
400 |
400 |
500 |
600 |
600 |
600 |
L |
mm |
250 |
400 |
400 |
500 |
600 |
900 |
1200 |
H |
mm |
120 |
120 |
150 |
150 |
200 |
220 |
220 |
Housing Material
|
一 |
Stainless steel
|
Main Filter
|
一 |
0.3μm 99.99%(DOP) |
Power Supply
|
一 |
1Φ 220 ,60Hz |
Wind Level
|
m3/min |
1 |
3 |
3.5 |
6.6 |
10.7 |
16 |
22 |
Wind Speed
|
m/s |
0.3 |
0.35 |
0.4 |
0.5 |
0.55 |
0.55 |
0.55 |
Power Consumption
|
Watt |
35 |
50 |
70 |
72 |
75 |
84 |
90 |
Currency
|
A |
0.25 |
0.27 |
0.3 |
0.32 |
0.3 |
0.38 |
0.42 |
Motor
|
一 |
Micro motor
|
External-rotor motor
|
Fan
|
一 |
Axial fan
|
High-efficiency backward centrifugal fan
|
Weight
(Main filter excluded)
|
Kg |
5 |
7 |
10 |
12 |
15 |
16 |
20 |
Power Supply External Wiring
|
一 |
Quick connector |
Overload Protection
|
一 |
Motor built-in temperature protection switch (1b,auto-relay) |
Optional Accessory
|
一 |
- Failure dry point and indicator
- Four-step speed control
- Step-less speed control
- Filter replaced to be |
Remarks: Custom-made available based on required dimensions and designs
|